Surveillance system
Location:Home > Product > Electric Power Supply Monitor > Surveillance system
DlJK-II Complex Monitor System
Classification:Surveillance system
Description:
Hotline:
0755-36615601
Characteristics
Parameter
Model type
Structure
Wiring
*The monitor can manage 2 group batteries at the the same time, and can monitor 2 sections bus data;
*Big touch screen truecolor liquid crystal display, Chinese graphics control and help menu, ensure the system operation is flexible and simple, English and Chinese menu are optional;
*Multiple communication modes:LAN、RS232、RS485、CAN etc, are fit for different system's communication demands, support CDT、RTU、MODBUS、IEC103 etc various protocols, is easy to access to remote monitor system;
*Multiple fault alarm functions: when the system become abnormal immediately sound and light alarm, and report to the background, the alarm value can be set freely, the alarm record automatically store;
*Multiple extensible I/O interface, can use to alarm output and other information's collection and controlling;
*Function module unitization design, detect mutual isolation between unit, high reliability, expand conveniently, it is convenient to install, use, preserve.
* Power supply voltage: DC 80~320V
* Input power: ≤5W
* Connection port and power collection:
Remote communication interface RS485 1 way、RS232 1 way
Intelligent equipment interface RS485 3 way; CAN bus interface 2 way;LAN interface 1 way
Dry contact output: 5 way Switching value feed-in: 20 way
AC voltage collection: 1 section 3 phase
DC voltage collection: 3 way voltage
DC current collection: 2 way current
Standby voltage collection: 7 way
Clock proofreading accept port: 1 way
* Battery management:
Intelligent equalized charging and floating charge convert
Fixed time equalized charging
Battery charge and discharge capacity calculate
Charge current-limiting
Temperature compensation
Battery capacity testing function
Battery charge and discharge characteristics curve display
* Working environment temperature: -5℃~+40℃
* Control function:
Charging module output voltage adjust
* System insulation detecting function:
Positive and negative bus voltage to ground and ground resistance
Matching with intelligent leakage current sensor can detect the brand way and insulation resistance to ground
* Alarm function:
Fault sound and light alarm , meantime report to background Alarm dry contact output
500 pieces historical alarms and 500 pieces battery records
* Insulation strength:
Communication port to case withstanding voltage 500VAC/1Min
Power supply port to case withstanding voltage 2000VAC/Min
Power supply port and communication port withstanding voltage 2500VAC/1Min
* Case dimension(L)×(W)×(H): 260mm×1 55mm×4 5mm
* Complete machine weight: ≤1kg
Charging module current-limiting
Output equalized charging/floating charge voltage convert
1.DLJK-II complex monitor system
2.DLJK-III integration?monitor system