Surveillance system
Location:Home > Product > Electric Power Supply Monitor > Surveillance system
DlJK-V PLC Monitor System
Classification:Surveillance system
Description:
Hotline:
0755-36615601
Characteristics
Parameter
Model type
Structure
Wiring
*Man-machine interface is friendly, adopt international brand 10.4 inch big touch screen liquid crystal display, Chinese dynamic graphical menu control and help menu, ensure the system operation is flexible and simple, Chinese and English menu are optional;
*According to three-level monitor system to design, AC data、 DC data、switching value feed-in(feed-out)、battery data、system insulation data can obtain through the communication of PLC and corresponding JLCL AC measuring unit、ZLCL DC measuring unit、
KGCL switching value measuring unit、BAT battery inspection unit、JYCL insulation measuring unit. Data collection and controlling singly collect and send, anti-interference ability is strong, is easy to extend;
*The whole course is dynamically track、display、control and record the course of battery's charge and discharge, online monitor system's current、voltage、temperature、alarm value and equalized charging、floating charge、insulation etc statement, automatically do temperature compensation;
*The operation parameters can be freely set and modified by users, the system has the password setting function;
*Multiple fault alarm functions: when the system become abnormal immediately send sound and light alarm, and report to background,
the alarm value can be set freely, the alarm record automatically store
*Support CDT、RTU、MODBUS、IEC103 etc various protocols, is easy to access to remote monitor system;
*Controlling software modifying is flexible, can modify according to the users' demand;
*Many controlling solutions, apply to multiple connection solutions in DC system;
*Comply with high grade anti-interference international standard, work is stable and reliable.
* Power supply voltage: DC 80~320V
* Input power: ≤10W
* Connection port and power collection:
Monitor is according to Germany Siemens S7-200 PLC use instruction
Display subject to the actual use of the man-machine interface
* Battery management:
Intelligent equalized charging and floating charge convert
Charge current-limiting
Fixed time equalized charging
Temperature compensation
Battery charge and discharge capacity calculate
Battery capacity testing function
Battery charge and discharge characteristics curve display
* Working environment temperature: -5℃~+40℃
* Control function:
Charging module current-limiting
Charging module output voltage adjust
* System insulation detecting function:
Positive and negative bus voltage to ground and ground resistance
Matching with intelligent leakage current sensor can detect the brand way and insulation resistance to ground
* Alarm function:
Fault sound and light alarm, meantime report to background
Alarm dry contact output
500 pieces historical alarms and 500 pieces battery records
* Insulation strength:
Communication port to case withstanding voltage 500VAC/1Min
Power supply port to case withstanding voltage 2000VAC/Min
Power supply port and communication port withstanding voltage 2500VAC/1Min
* Case dimension(L)×(W)×(H): 320mm×185mm×65mm
* Complete machine weight: ≤1kg
Output equalized charging/floating charge volta ge convert
DLJK series electric power supply monitors' models in Xinruida:
1.DLJK-II complex monitor system
2.DLJK-III integration monitor system
Purchase:DlJK-V PLC Monitor System