Insulation Monitor
Location:Home > Product > Insulation Monitor
JYCL2.1 Insulation Monitor
Classification:Insulation Monitor
Description:
Hotline:
0755-36615601
Characteristics
Parameter
Model type
Structure
Wiring
*Adopt our company exclusively high accuracy intelligent leakage current sensor, connection is very simple;
*Bus voltage insulation measures, avoids the interference cause fault alarm;
*48V、110V、220V system used universally, accuracy grade: bus voltage to ground is 0.2, bus insulation resistance is 2, branch way insulation resistance is 3;
*Bus insulation response alarm time≤3S;
*Branch way insulation response alarm time≤20S;
*RS485 communication interface, standard MODBUS communication protocol;
*Modular design, expansion is convenient, can match with 1~10 pieces insulation detection collection module, achieves the insulation measurement of two sections bus 2400 branch ways
JYCL2.1 Insulation Monitor |
|||
Function Items Parameter |
Parameter Range |
Grade |
Note |
Power Supply |
90~300VDC or 85~250VAC |
|
|
Power Consumption |
<10w |
|
|
Working Environment Temperature |
-5~+50℃ |
|
|
Working Relative Humidity |
10%RH~90%RH |
|
|
Atmospheric Pressure |
70~106kpa |
|
|
Machine Dimension(L)×(W)×(H) |
210mm×118mm×84mm |
|
|
Weight |
About910g |
|
|
Communi cation Interface |
RS4 85 |
|
|
Communication Baud Rate |
1200、4800、9600、19200bps can be set |
|
|
Bus Voltage To Ground Measurement |
0~300V |
±0.2% |
|
Bus Insulation Resistance Measurement |
0~100K |
±2% |
Our company supply the intelligent leakage current sensor to accomplish |
Branch Way Insulation Resistance Measurement |
0~75K |
±2% |
Our company supply the intelligent leakage current sensor to accomplish |
Branch Way Detection Time |
100ms/ 1 way |
|
|