Insulation Monitor
Location:Home > Product > Insulation Monitor
JYCL2.6 Insulation Monitor
Classification:Insulation Monitor
Description:
Hotline:
0755-36615601
Characteristics
Parameter
Model type
Structure
Wiring
*Adopt our company exclusively high accuracy analog intelligent leakage current sensor, measurement is accurate and stable, innovative online zero self-adjustment design, solve the difficulty of the engineering construction;
*Bus voltage insulation measure, avoid the interference cause fault alarm;
*EMS performance conforms to the IEC61000-6-2 industrial environment anti-interference standards;
*48V、110V、220V system used universally, accuracy grade: bus voltage to ground is 0.2, bus insulation resistance is 2, branch way insulation resistance is 3
*Bus insulation response alarm time≤3S;
*Branch way insulation response alarm time≤20S;
*RS485 communication interface, standard MODBUS communication protocol, the PC communication protocol can be
customized, it convenient for other factory to connect with the monitor, this product is compatible with EMERSON monitor;
*Modular design, expanding is convenient, can match with 1~10 pieces insulation detection collection module, can achieve the insulation measurement of one section bus 1200 branch ways;
*Products conforms to the IEC61000-6-2 ROHS lead-free standard, through the CE certification,
JYCL2.6 Insulation Monitor |
|||
Function Items Parameter |
Parameter Range |
Grade |
Note |
Power Supply |
90~300VDC or 85~250VAC |
|
|
Power Consumption |
<15w |
|
Match with less than 20 branch way sensors |
Working Environment Temperature |
-10~+50℃ |
|
|
Working Relative Humidity |
10%RH~90%RH |
|
|
Atmospheric Pressure |
70~106kpa |
|
|
Machine Dimension(L)×(W)×(H) |
216mm×94mm×38.5mm |
|
|
Weight |
About600g |
|
|
Communi cation Interface |
RS485 |
|
|
Communication Baud Rate |
1200、4800、9600、19200bps can be set |
|
|
Bus Voltage To Ground Measurement |
0~450V |
±0.2% |
|
Bus Insulation Resistance Measurement |
0~100K |
±2% |
|
Branch Way Insulation Resistance Measurement |
0~75K |
±4% |
Our company supply the intelligent leakage current sensor to accomplish |
Auxiliary power output |
+12V,1000mA |
|
|
Insulation resistance alarm threshold |
5~25K |
|
Default:25k |
Two way dry contact output |
Contact capacity:DC30V/1A, AC125V/0.5A,switch power:30W |
|
Provide two way mutual exclusion output |