Insulation Monitor
Location:Home > Product > Insulation Monitor
JYCL5.0 Insulation Monitor
Classification:Insulation Monitor
Description:
Hotline:
0755-36615601
Characteristics
Parameter
Model type
Structure
Wiring
fall situation;
*Adopt our company exclusive high accuracy intelligent leakage current sensor, connection is very simple, monitoring branch way can expand to 600 ways;
*Bus voltage isolation measure, avoids interference cause fault alarm;
*48V、110V、220Vsystem used universally, accuracy grade: bus voltage to ground is 0.2, bus insulation resistance is 2, branch way insulation resistance is 2, bus insulation response alarm time≤3S, branch way insulation response alarm time≤20S;
*Multiple communication modes: LAN、RS232、RS485 etc. are fit for different system's communication demands;
*Multiple fault alarm functions: when the bus and branch ways above limit acousto-optic alarm, the alarm value can be set freely, the alarm record automatically store.
*Multiple extensible I/O entrance, can be used to alarm output and other information's collecting and controlling
*Production compliance and EMC comply with CE certification.
JYCL5.0 Insulation Monitor |
|||
Function Items Parameter |
Parameter Range |
Grade |
Note |
Power Supply |
90~300VDC or 80~250VAC |
|
|
Power Consumption |
<10w |
|
Match with less than 20 branch way sensors |
Working Environment Temperature |
-10~+50℃ |
|
|
Working Relative Humidity |
10%RH~90%RH |
|
|
Atmospheric Pressure |
70~106kpa |
|
|
Machine Dimension(L)×(W)×(H) |
260mm×155 mm×45mm |
|
|
Weight |
About750g |
|
|
Communi cation Interface |
RS485 |
|
|
Communication Baud Rate |
1200、4800、9600、19200bps can be set |
|
|
Bus Voltage To Ground Measurement |
0~300V |
±0.2% |
|
Bus Insulation Resistance Measurement |
0~100K |
±2% |
|
Branch Way Insulation Resistance Measurement |
0~75K |
±4% |
Our company supply the intelligent leakage current sensor to accomplish |
Branch Way Detection Time |
100ms/ 1 way |
|
|